Self diagnosis function

We are constantly trying to do better service to our customers by installing such judges that show abnormality of each function as follows:

Outdoor heat exchanger fluid pipe
sensor error

Outdoor temperature sensor error

• Broken outdoor sensor wire, poor connector connection

Description of trouble

Room temperature sensor error

Cause

• Broken heat exchanger sensor (1) wire, poorconnector

connection

• Disconnected sensor

Indoor fan motor error

Heat exchanger sensor (1) error

2 time flash

5 time flash

TIMER lamp ON

1 time flash

RUN lamp

2 time flash

1 time flash

TIMER lamp

RUN lamp keeps flashing

• Broken room temperature sensor wire, poor connector connection

• Defective fan motor, poor connector connection

• Broken heat exchanger fluid pipe sensor wire, poor connector

connection

Characteristics of HEAT mode operation

Mechanism and capacity of HEAT mode operation

Mechanism

• The unit draws in heat from the cold outside air, transfers it indoors and heats the room. The heating capacity of the heat pump mechanism decreases

when the outside air temperature gets colder.

• The hot air circulation system takes a while before warming up the room temperature.

• If the outside temperature becomes extremely low, it would be better to use an additional source of heating.

Defrosting

If the outside temperature becomes low and humidity is high, the heat exchanger in the outdoor unit may frost over, which prevents efficient heating.
If this happens, the automatic defroster is activated and during defrosting the heating operation stops for 5 to 10 minutes.
• Both indoor and outdoor fans stop and the RUN light (green) blinks slowly (1.5 sec. ON, 0.5 sec. OFF) during defrosting.
• The outdoor unit may give off some steam during defrosting. This is to help the defrosting process and is not a defect.

• The HEAT operation resumes as soon as defrosting has been completed.

2 time flash

RUN lamp 2 time flash

Rotor lock

• Defective compressor
• Open phase on compressor
• Defective outdoor unit boards

• If heating operation is performed when the outside temperature is high, room temperature may become higher than the set temperature.

Trouble of outdoor unit

Over current

• Compressor locking, open phase on compressor output,

shortcircuit on power transformer, closed control valve

Current cut

2 time flash

3 time flash

1 time flash

Over heat of power transistor

Over heat of compressor

4 time flash

5 time flash

RUN lamp ON

• Broken power transformer, broken compressor wire
• Broken discharge pipe sensor wire, poor connector connection
• Compressor blockage

• Overload operation, overcharge

• Cooling problem

• Gas shortage, defective discharge pipe sensor, closed control

valve

6 time flash

Error of signal transmission

• Defective power supply, Broken signal wire, defective in/outdoor

unit boards

Discharge pipe sensor error

• Broken discharge pipe sensor wire, poor connector connection

Suction pipe sensor error

• Broken suction pipe sensor wire, poor connector connection

• Broken power transistor sensor wire, poor connector connection

Power transistor sensor error

4 time flash

5 time flash

6 time flash

6 time flash

7 time flash

Heat exchanger sensor (2) error

• Broken heat exchanger sensor (2) wire, poor connector

connection

• Disconnected sensor

Closed service valve

Heat exchanger sensor (1) error

• Closed service valve
• Disconnected sensor