9

PowerSupplyRequirements

Check the power supply against the model number before applying

power to the instrument. DI50 displays must be used with a suitable
mains Power Supply, ratings are as follows:

Voltage Range

Nominal Voltage

Power

Frequency

100–132 V AC

110 V AC

6 VA

47-63 Hz

200–264 V AC

240 V AC

6 VA

47-63 Hz

12–35 V DC*

24 V DC

4.5 W (at 24 V DC)

-

*Using a DC power supply that provides this voltage will comply with
the instrument’s UL/CSA listing.

Connections

For effective protection from electromagnetic noise, all signal cables

must be shielded, or located on conductive trays or in conduits.

Use 1-8 AWG Cu Wire rated for temperatures above 70 °C Only,

tighten to 4.5 lb-In. Strip wires to 7 mm from the ends. Use a suitable
ferrule for multistranded wires (do not solder).

Terminal

Signal

1

+24 V DC

Sensor power supply (Output)

2

0V

3

Signal +

Analogue Input

4

Signal −

7

Live (+)

Power Supply

8

Neutral (−)