Weidmuller DI350 - Display instrument for control panel Benutzerhandbuch
Seite 9

9
PowerSupplyRequirements
Check the power supply against the model number before applying
power to the instrument. DI50 displays must be used with a suitable
mains Power Supply, ratings are as follows:
Voltage Range
Nominal Voltage
Power
Frequency
100–132 V AC
110 V AC
6 VA
47-63 Hz
200–264 V AC
240 V AC
6 VA
47-63 Hz
12–35 V DC*
24 V DC
4.5 W (at 24 V DC)
-
*Using a DC power supply that provides this voltage will comply with
the instrument’s UL/CSA listing.
Connections
For effective protection from electromagnetic noise, all signal cables
must be shielded, or located on conductive trays or in conduits.
Use 1-8 AWG Cu Wire rated for temperatures above 70 °C Only,
tighten to 4.5 lb-In. Strip wires to 7 mm from the ends. Use a suitable
ferrule for multistranded wires (do not solder).
Terminal
Signal
1
+24 V DC
Sensor power supply (Output)
2
0V
3
Signal +
Analogue Input
4
Signal −
7
Live (+)
Power Supply
8
Neutral (−)