Electricalconnectionslabel

The DPA Series of instruments are often customised specifically for

your application. Check the label on top of the case for the correct
connections.

Alarmconnections

The DPA has a high inbuilt immunity to noise spikes caused by

switching inductive loads like solenoids or relay coils. However, it
is important to use suppression capacitors across inductive loads
to preserve the relay contacts and to reduce the effect of switching
spikes on nearby circuits. The alarm outputs are dual SPDT relay
contacts with built in suppression capacitors fitted across the normally
open and common contacts.

Cablepreparationandinstallation

For effective protection from electromagnetic noise, all signal cables

must be shielded, or located on conductive trays or in conduits.

Use 1-8 AWG Cu Wire rated for temperatures above 0 °C Only,

tighten to 4. lb-In. Strip wires to  mm from the ends. Use a suitable
ferrule for multistranded wires (do not solder).

InputSignalCabling

Use suitable twisted pair cable for the input signal connection.