Deadband(DBControl)adjustment

The deadband control adjusts the point at which a tripped alarm

resets. This point will be above the setpoint for a low type alarm or
below for a high type. The procedure for adjusting the DB control is as
follows:

1. Adjust the SET control as above.
. Set source B to 4 mA.
. Set the deadband to maximum by turning the DB control fully

clockwise.

4. Trigger the alarm by setting source A to 0 mA (for a high type

alarm) or 4 mA (for a low type alarm).

. Set source A to give the differential current at which the alarm

should reset.

6. Decrease the deadband (turn control anticlockwise) until the LED

extinguishes.

. Check that the setpoint and deadband are set correctly.

Internalsettings(Alarmtypeandcoilenergisation)

To change the alarm type or coil energisation:
1. Remove the left hand side plate.
. Set the links according to the diagram (right).
. Replace the side plate.