1 terminalconnectionsforcalibration – Weidmuller TWI-2 - Signal isolator in 2-wire design, 2-channel Benutzerhandbuch

Seite 13

Advertising
background image

1

Terminalconnectionsforcalibration

ModelNumber

Cat.No.

Channel

Signal

Signaltype

Terminal

TWI-2/4-20 mA

7940010171

One

4-20 mA input

DC milliamp source +

1

DC milliamp source −

2

4-20 mA output

mA output +

5

mA output −

6

Two

4-20 mA input

DC milliamp source +

3

DC milliamp source −

4

4-20 mA output

mA output +

7

mA output −

8

TWI-2/0-10 V

7940012011

One

0-10 V input

DC voltage source +

1

DC voltage source −

2

4-20 mA output

mA output +

5

mA output −

6

Two

0-10 V input

DC voltage source +

3

DC voltage source −

4

4-20 mA output

mA output +

7

mA output −

8

Note: check all connection details against the instrument top label.

ZeROandSpANadjustment

The ZERo and SPAN controls are on the front panel of the transmitter.

Turn the control clockwise to increase the output level.

1. Connect up the instrument according to the table above.
. Set the input source to 0.00 V or 4.00 mA.
. Turn the ZERo adjustment until the output is at 4.00 mA.
4. Set the input source to 10.00 V or 0.00 mA.
5. Adjust the SPAN control until the output is at 0.00 mA.
6. Recheck the ZERo adjustment.