TWI-2

•Operation

general

The TWI- is a dual channel, DIN rail mount, loop powered, signal

Isolator/Converter for current/voltage signals.

Loop powered transmitters use the drop in voltage across the outputs

to generate power for the electronics. The TWI requires at least a 1 V
drop to operate correctly.

Receiving devices are placed in series with the TWI and introduce

additional load resistances into the loop. The total loop load for a

4-0 mA loop powered by supply voltage V

s

is R

loop

= 50 x (V

s

-1).

So, for example, a TWI powered from a 4 V DC supply can drive

600 Ω loop load.

Cleaning

The case can be wiped with a damp cloth. De-energise the unit before

cleaning.

Receiving

device

(Current

inputs)

Power

Supply

− +

Twisted pair cable

Loop

Powered

Transmitter

+

+ −

Connection diagram for loop powered transmitter outputs.