Setupsequence – Weidmuller UCVR - Universal glavanically isolated signal converter Benutzerhandbuch

Seite 19

Advertising
background image

1

•SetupSequence

Setting

Display

Description

Е м

ENT

S/W Version

v3.01

S/W Version 3.01 (Note: this information only applies to versions
3.00 to 3.09)

DisplayandInputs

Input type

IP=1

IP=E

Current (mA)
Voltage (V)

Toggle

Accept

Maximum

input range

rng=

5

10

20

50

Introduces the setting
-5.500 to +5.500 mA or V
-11.00 to +11.00 mA or V
-22.00 to +22.00 mA or V
-55.00 to +55.00 mA or V

Toggle

Accept

Input range

InL=

4.00

Input range lower limit
e.g., 4.00 mA

-

Dec

-

Inc

Next

Accept

InH=

20.00

Input range upper limit
e.g., 20.00 mA

-

Dec

-

Inc

Next

Accept

Input

Calibration?

CIPn

CIPy

Skip input calibration
Calibrate the inputs

Toggle

Accept

Transfer
function

FnC=

LInr

Sr

Introduces the transfer function
Linear
Square root

-

Toggle
Toggle

-

Accept
Accept

Damping factor

dF=

2

Introduces the damping factor
Value, e.g., 2

-

Dec

-

Inc

Next

Accept

Display range

dP=

.

Decimal point position

-

Shift

Next

Accept

dLO=

0.0

Display range lower limit
e.g., 0.0

-

Dec

-

Inc

Next

Accept

dHI=

100.0

Display range Upper limit
e.g., 100.0

-

Dec

-

Inc

Next

Accept