Setupsequence(continued) – Weidmuller UHZR - Universal glavanically isolated signal converter Benutzerhandbuch
Seite 18

18
Alarmchannelone
Coil energisation
A1nE
A1nd
Normally energised
Normally de-energised
Toggle
Accept
Alarm type
A1=L
A1=H
Low type (active below setpoint)
High type (active above setpoint)
Toggle
Accept
Setpoint value
SP1=
50.0
Setpoint value
e.g., 50.00 %
-
Dec
-
Inc
-
Next
Accept
Deadband value
db1=
0.1
Deadband value
e.g., 0.01 %
-
Dec
-
Inc
Next
Accept
Timer delay
dL1=
20
Timer delay (set to 0 s to disable)
e.g., 20 s
-
Dec
-
Inc
Next
Accept
Alarmchanneltwo
Coil energisation
A2nE
A2nd
Normally energised
Normally de-energised
Toggle
Accept
Alarm type
A2=L
A2=H
Low type (active below setpoint)
High type (active above setpoint)
Toggle
Accept
Setpoint value
SP2=
50.0
Setpoint value
e.g., 50.0 %
-
Dec
-
Inc
-
Next
Accept
Deadband value
db2=
10.0
Deadband value
e.g., 10.0 %
-
Dec
-
Inc
Next
Accept
Timer delay
dL2=
20
Timer delay (set to 0 s to disable)
e.g., 20 s
-
Dec
-
Inc
Next
Accept
Generalalarmsettings
Alarm reset
sequence
nOr
rES
Automatic reset
Manual reset
Toggle
Accept
Setpoint
security
SECy
SECn
Setpoints fixed at setup
Can change setpoints
Toggle
Accept
Save values
SAVE
Instrument is saving the changes to the setup and returning to normal
operation
SetupSequence(continued)