•Setup
Changingthesetup
For setup mode, connect the security link and press the
Å
and
ì
keys simultaneously. The software version will be displayed (flashing). If
you wish to continue, press within 10s.
During setup the
Å
and
ì
keys change values and toggle options.
The key accepts changes and moves to the next item in the setup
sequence (see table).
Note: If you remove the security link during the setup sequence, any
changes you have made will be discarded.
SetupSequence
Setting
Display
Description
Е м
ENT
S/W Version
v1.01
S/W Version 1.01 (Note: this information only applies to versions
1.00 to 1.09)
DisplayandInputs
Input type
IP=1
IP=2
IP=3
IP=4
IP=5
IP=6
IP=7
IP=8
IP=9
J Type Thermocouple
K Type Thermocouple
N Type Thermocouple
T Type Thermocouple
E type Thermocouple
B Type Thermocouple
S Type Thermocouple
R Type Thermocouple
millivolt signals (no CJC)
Next Prev Accept
Display units
dEgC
dEgF
-
Degrees Celsius
Degrees Fahrenheit
Skipped for mV inputs/display
Toggle
Accept
Display range
dHI=
870
Introduces display high value
Value, e.g., 870 °C
Toggle
Accept
dLO=
-50
Introduces display low value
Value, e.g., -50 °C
Toggle
Accept
Damping factor
dF=
2
Introduces the damping factor
Value, e.g., 2
-
Dec
-
Inc
Next
Accept