Programming plan, Ta202 – Baumer TA202 Benutzerhandbuch
Seite 15

TA202
www.baumer.com
15
9. Programming plan
line 11-16 status for lines 1-6
0 * Alter parameter
1
Lock of delete resp.enter
2
Skip parameter
line 21
Calcuating functions
0 * Relation tacho F1 : tacho F2
1
difference tacho F1 - tacho F2
2
stretching / compression
3
Flow time (length)
4
Time measurement - Start/Stopp
5
Time measurement – period
6
Time measurement – pulse duration
7
Pulse rate measurement
line 22
Inversion of calculating function
0 * Calculating function as above
1
inverted F1->F2 F2->F1
line 23
Count mode tacho for F1 and F2
0 * F1 Track A with Up/Down F2 40 kHz
1
F1 Track A 90° B F2 40 kHz
2
F1 Track A with Up/Down F2 25 Hz
3
F1 Track A 90° B F2 25 Hz
line 24
Input logic (for F1 and F2)
0 * PNP Trigger level approx. 11V
1
NPN Trigger level approx. 11V
2
PNP Trigger level approx. 5V
3
NPN Trigger level approx. 5V
4
PNP Trigger level approx. 2,5V
5
NPN Trigger level approx. 2,5V
line 25
Evaluation tacho F1
0.0001
Min.
1.0000 * Default
9999.99
Max.
line 26
Evaluation tacho F2
0.0001
Min.
1.0000 * Default
9999.99
Max.
line 27
Factor for calculation function F3
0.0001
Min.
1.0000 * Default
9999.99
Max.
line 28
minimum update time for F1-F3
0
Maximum update time (approx. 0,5s)
1 * 1 second
2
2 Seconds
3
3 Seconds
4
5 Seconds
5
10 Seconds
6
20 Seconds
7
30 Seconds
8
60 Seconds
line 29
Time out for F1-F3
0 * 1 second
(0,1S)
1
2 Seconds
(0,2s)
2
3 Seconds
(0,3s)
3
5 Seconds
(0,5s)
4
10 Seconds
(1s)
5
20 Seconds
(2s)
6
30 Seconds
(3s)
7
60 Seconds
(6s)
8
Time-out function out of order
(8s)
9
as 8 but store
(10s)
line 30
Time unit tacho F1
0 * 1/min
1
1/s
2
1/h
line 31
Time unit tacho F2
0 * 1/min
1
1/s
2
1/h
line 32
Assignment of dragging value
0 * F1
1
F2
2
F3
line 33
Assignment output 1
0 * Upper Limit value tacho F1
1
Lower Limit value tacho F1
2
Upper Limit value tacho F2
3
Lower Limit value tacho F2
4
Upper Limit value calculating function F3
5
Lower Limit value calculating function F3
line 34
Assignment output 2
0 * Upper Limit value tacho F1
1
Lower Limit value tacho F1
2
Upper Limit value tacho F2
3
Lower Limit value tacho F2
4
Upper Limit value calculating function F3
5
Lower Limit value calculating function F3
line 35
Output logic for digital output
0 * Both outputs as normally closed
1
Out 1 open, Out 2 closed
2
Out 1 closed, Out 2 open
3
Both outputs as normally open
line 36
Decimal point for tacho F1
0 * No decimal point
1
00000.0
2
0000.00
3
000.000
line 37
Decimal point for tacho F2
0 * No decimal point
1
00000.0
2
0000.00
3
000.000
line 38
Decimal point for calculating function F3
Calc. func. 0-2,7
Calc.func. 3-6
0 * No decimal point
59.59.99 min
1
00000.0
99.59.59 h
2
0000.00
"
3
000.000
"
line 39
Basic display selection
0 * No switchover to basic display
1
F1
2
F2
3
F3
4
SZ
5
P1
6
P2
line 40
Code
0000 * Code not active
:
9999
line 41
Function key assignment
0 * Function key not assigned
:
6
Maximum value (line 6)
line 42
Output reaction of lower limit value
1 * with contact lock
0
W/o contact lock
line 51
Baudrate
0 * 4800 Baud
1
2400 Baud
2
1200 Baud
3
600 Baud
line 52
Parity
0 * Even Parity
1
Odd Parity
2
No Parity
Line 53
Stop bits
0 * 1 Stop bit
1
2 Stop bits
Line 54
Device address
00 * Minimum value
:
99
Maximum value