9. Parameterization plan
Zl 11-17
Status for lines 1-7
0
Parameter change enabled
1
Parameter lock (entry,clearing)
2
Skip parameter
Line 22
Operating modes
0
Step preset
1
Main preset
2
Parallel comparison
3
P1-dragged preset
Line 24
Decimal point
0
No decimal point
1
00000.0
2
0000.00
3
000.000
4
00.0000
Line 25
Count mode
0
Track A resp. UP/DOWN-signal on track B
1
Subtracting (A-B)
2
Adding (A+B)
3
Track A 90° B single evaluation
4
Track A 90° B double evaluation
5
Track A 90° B four times evaluation
Line 26
Frequency main counter track A
0
10 kHz
1
25 Hz
2
3 Hz
Line 27
Frequency main counter track B
0
10 kHz
1
25 Hz
2
3 Hz
Line 28
Input logic
0
PNP - Trigger threshold 10V
1
NPN - Trigger threshold 10V
2
PNP - Trigger threshold 5V
3
NPN - Trigger threshold 5V
4
PNP - Trigger threshold 2,5V
5
NPN - Trigger threshold 2,5V
Line 29
Reset main counter (control input 1)
0
Automated reset and ext. static
1
Automated reset and ext. differntiated
2
Extern static
3
Extern differentiated
4
Extern with "Start-functionality"
Line 31
Functionality control input 2
0
Stop
1
Hold
2
Keylock
3
Hour counter on/off
4
Offset
5
Print (only with interface)
Line 33
Digital output logic
0
Both outputs normally closed
1
P1 Normally open, P2 Normally closed
2
P1 Normally closed, P2 Normally open
3
Both outputs Normally open
Line 35
Latch signal duration P1
0.25
Default
0.01
Min.
99.99
Max.
Line 36
Latch signal duration P2
0.25
Default
0.01
Min.
99.99
Max.
Line 37
Preset P1, P2 adoption
0
Immediately effective
1
After reset
Line 38
Counting range P1,P2 and SC
0
Only positive
1
Positive and negative
Line 39
Function key assignment
0
Not operational
1
XP
2
P1
3
P2
4
SC
5
Σ
6
§
7
SF
Line 40
Code
0000
Code not active
:
9999
Line 41
Functionality batch counter
0
Totalizer
1
When achieving P2
Line 42
Multiplier batch counter (Line 41=1)
1
Default
0
Min.
999
Max.
Line 43
Offset
0
No offset
:
999999
Max. offset
Line 44
Power loss warning
0
No warning
1
warning (display flashing)
Line 51
Baudrate
0
4800 Baud
1
2400 Baud
2
1200 Baud
3
600 Baud
Line 52
Parity
0
Even Parity
1
Odd Parity
2
No Parity
Line 53
Stoppbits
0
1 Stoppbit
1
2 Stoppbits
Line 54
Adresse
00
Default
00
Min.
99
Max.
Line 55
Output assignment via interface
Line 31=5
0
Displayed value
1
XP
2
P1
3
P2
4
SC
5
Σ
6
§
7
SF
Line 56
RS422: connections TxD+ , TxD-
0
In transmission direction during trans-
mission, in receiving direction upon
receipt
1
Ever in transmission direction