Information on mounting and operation – WIKA T24 Benutzerhandbuch

Seite 23

Advertising
background image

GB

WIKA operating instructions temperature transmitter, model T24

23

2370242.09 08/2013 GB/D

8. Information on mounting and operation in

hazardous areas (Europe)

In hazardous areas, only use temperature transmitters that are

approved for those hazardous areas. The approval is marked on the

product label.

8.1 Model overview of European approvals

Head mounting

version

Ex protection and

Approval No.

Ignition

protection type

T24.10.xx2

II 1G EEx ia IIB/IIC T4/T5/T6

DMT 02 ATEX E 025 X

intrinsically safe

equipment

T24.10.xx9

II 3 G Ex nA IIC T4…T6

energy-limited

equipment

II 3 G Ex nL IIC T4…T6

non-sparking

equipment

II 3 G Ex ic IIC T4…T6

intrinsically safe

equipment

8.2 Specific conditions for safe use
T24.10.xx2
: Transmitters in a hazardous area should only be powered

by associated intrinsically safe apparatus that are approved for the

relevant hazardous area. The temperature transmitter must be mounted

in an enclosure that meets a minimum ingress protection of IP 20 per

EN 60529/IEC 529.

T24.10.xx2 for category II 1G/IIC in addition: The surface of

the casing is not conductive. The temperature transmitter must be

mounted in such a way that no electrostatic charging can occur. This is

ensured, for example, by mounting the transmitter into an electrically-

conductive connection head.