3. Specifications

Alarm outputs 1 (A1) and 2 (A2)
Alarm behaviour:

no alarm, high alarm, low alarm, high alarm with standby,

low alarm with standby (selectable)

Operating principle: On/Off
Hysteresis:

0.1 ... 100 °C (°F) or 1 ... 1,000 °C (°F)

(the position of the decimal point corresponds to the input

configuration)

Output:

Relay

Load capacity AC 250 V, 3 A (resistive load)

Service life 100,000 load cycles

Alarm output 3 (A3)
Alarm behaviour:

no alarm, high alarm, low alarm, high alarm with standby,

low alarm with standby, high/low alarm (selectable)

The high/low alarm can only be selected if alarm 1 has been

configured as high alarm (high alarm with standby) and alarm 2 as

low alarm (low alarm with standby) or vice versa.

Operating principle: On/Off
Hysteresis:

0.1 ... 100 °C (°F) or 1 ... 1,000 °C (°F)

(the position of the decimal point corresponds to the input

configuration)

Output:

Relay

Load capacity AC 250 V, 3 A (resistive load)

Service life 100,000 load cycles

Analogue actual-value output signal

The input value is converted to an analogue signal every 0.25 seconds and output as

a DC signal. If the output signal is being used as an input for other instruments, the

maximal load must not be exceeded.

Resolution:

1/12,000

Output signal: 4 ... 20 mA (permissible load max. 500 Ω)

Accuracy:

±0.3 % of the output span