6. Commissioning, operation

Auxiliary parameter level 2

In order to configure the auxiliary parameter level 2, first press △+▽-key and additionally

the MODE key for 3 seconds. To switch to the next parameter, press MODE key once

again. After setting up the final parameter, exit the menu by pressing the MODE key.

Display

Name, function and setting range

Factory setting

Input configuration

The multi-function input can be configured for thermocouples

(10 types) and resistance thermometers (2 types) with the units

°C/°F and also for current signals (2 types) and voltage signals

(4 types).

Before changing the input configuration from a voltage input to a

different input signal, disconnect the sensor from the instrument.

Only then change the input configuration. If the input configuration

is altered with a connected sensor, the measuring input can be

damaged.

For setting ranges see table “Setting ranges of the input configura-

tion” under this chapter.

Type K

(-200 ... +1,370°C)

End value scaling

Scaling the end value

Setting range: scaled start value to max. possible end value

Only available with current and voltage signals

9999

Start value scaling

Scaling the start value

Setting range: min. possible start value to scaled end value

Only available with current and voltage signals

-1999

Decimal point

Setting the decimal point

No decimal point:

1 figure after the decimal point

2 figures after the decimal point

3 figures after the decimal point

Only available with current and voltage signals

No decimal point

Time for the actual-value input filter

Input of the time for the actual-value input filter

During the set time, an averaging of the actual value is carried out.

If the value is set too high, this can affect the alarm function due to

the delay

Setting range: 0.0 ... 10.0 seconds

0.0 seconds

Alarm type alarm A1

Setting of the alarm type for alarm A1

- No alarm:
- High alarm:
- Low alarm:
- High alarm with standby:
- Low alarm with standby:

no alarm