WIKA operating instructions digital indicator, model DI25

14076218.01 12/2013 GB/D

GB

6. Commissioning, operation

Setting ranges alarm types

Alarm type

Setting range

High alarm

Start value to end value of the input configuration

Low alarm

Start value to end value of the input configuration

High alarm with standby

Start value to end value of the input configuration

Low alarm with standby

Start value to end value of the input configuration

High/low alarm

none

The high/low alarm ist only available for alarm A3.

Once the high/low alarm is selected, the settings in connection with A3

(A3 alarm value, A3 switch behaviour, A3 hysteresis, A3 delay time) will not be

indicated.

Setting ranges of the input configuration

TCs and RTDs

°C

°F

K

-200 ... +1,370 °C

-320 ... +2,500 °F

-199.9 ... +400.0 °C

-199.9 ... +750.0 °F

J

-200 ... +1,000 °C

-320 ... +1,800 °F

R

0 ... 1,760 °C

0 ... 3,200 °F

S

0 ... 1,760 °C

0 ... 3,200 °F

B

0 ... 1,820 °C

0 ... 3,300 °F

E

-200 ... +800 °C

-320 ... +1,500 °F

T

-199.9 ... +400.0 °C

-199.9 ... +750 °F

N

-200 ... +1,300 °C

-320 ... +2,300 °F

PL-II

0 ... 1,390 °C

0 ... 2,500 °F

C (W/Re5-26)

0 ... 2,315 °C

0 ... 4,200 °F

Pt100

-199.9 ... +850.0 °C

-199.9 ... +999.9 °F

JPt100

-199.9 ... +500.0 °C

-199.9 ... +900.0 °F

Pt100

-200 ... +850 °C

-300 ... +1,500 °F

JPt100

-200 ... +500 °C

-300 ... +900 °F