4 technical data for 2-wire transmitter, Technical data for 2-wire transmitter – JUMO 707030 dTRANS T03 2-Wire/3-Wire Transmitter Operating Manual Benutzerhandbuch

Seite 80

Advertising
background image

36

4 Technical data for 2-wire transmitter

Input for r

e

sistance thermometer

Measuring cir

c

uit monitoring

dTRANS T03 J

T

y

pe 707030/...

dTRANS T03 B

T

y

pe 707031/...

dTRANS T03 T

T

y

pe 707032/...

Measur

ement input

P

t100 (EN 60751)

Range limits

-200

to

+850

°C

Connection cir

c

uit

2

-wir

e cir

cuit

2-wir

e

or

3

-w

ire

c

irc

u

it

2

-w

ir

e

o

r 3

-w

ire

c

irc

u

it

Smallest span

25°C

Lar

g

est span

1050

°C

Unit

measuring range conf

iguration in °C or °F

Zer

o

shift

for spans < 75

°C

fi

xe

d zer

o

: -40

°C

, -20

°C

, 0

°C, 20

°C, 4

0

°C

a

a

-30

°C, -10

°C, 0

°C, 10

°C, 30

°C available upon request

for span



75

°C: ±50

°C

for spans > 75

°C: see page

34

Sensor lead r

e

sistance

for 3-wir

e

c

o

n

n

ecti

o

n

11

pe

r conductor

Sensor lead r

e

sistance

for 2-wir

e

c

o

n

n

ecti

o

n

factory-set:

0



lead r

e

sistance

settable thr

o

ugh setup pr

ogram

S

e

nso

r curr

ent

0.5

m

A

Sampling rate

continu

o

u

s

measur

em

ent because of analog signal path

Underran

ge

falling to

3.6

m

A

Overrange

rising to

 22

mA

to

 28

mA (typically 24

mA)

Pr

obe short-cir

c

uit

3.

6

m

A

Pr

obe and lead br

eak

positive:

 22

mA

to

 28

mA (typically 24

mA)

negative:

3.6

m

A