4 fuse change, Fuse change, Maintenance – Lenze EL 9700 Benutzerhandbuch

Seite 105: Danger

Advertising
background image

Maintenance

Repair

Fuse change

7

l

105

LDCDS−ELx7xx DE/EN 4.0

7.3.4

Fuse change

}

Danger!

Hidden damage possible after blowing of fuses
The baseboard (

68) is protected by a fuse which will be damaged if the

voltage applied is too high.
Possible consequences:

ƒ

The device can be damaged if a non−approved fuse is installed.

ƒ

In the event of a blowing fuse, hidden damage on the device cannot be ruled
out. Faultless operation can no longer be guaranteed.

Protective measures:

ƒ

The fuse may only be replaced by an approved type.

ƒ

In the case of safety−critical applications the device has to be checked by
Lenze after the blowing of fuses.

Approved types:

ƒ

Littelfuse, series 154, 4 A

POWER

FAN2

FAN3

CF-CARD

RESET

USB-μCON

BLIGHT

ACCU

CR2450

1

2

19

20

F1

T4A

0

ELx7xx−018

Proceed as follows:

1. Remove the mains cable (

87).

2. Open the housing (

100).

3. Remove the old fuse

0 from the holder.

4. Insert a new fuse

0 into the holder.

5. Close the housing (

87).

6. Plug in the mains cable (

100).