Electrical installation – Lenze ELCAFHIxxx4E34NNER Highline Benutzerhandbuch

Seite 68

Advertising
background image

Electrical installation

Power terminals

4

l

68

EDKLCFH3024−EER DE/EN 2.0

X21 − Motor connection

Pin

Connection

Description

Data

Connector: female, Harting HAN−Modular
Use Lenze system cable

a1

U1

Phase U1

Max. output voltage: mains voltage
Max. continuous output current:
dependent on type

a2

V1

Phase V1

a3

W1

Phase W1

c1

+PTC

Motor temperature monitoring

PTC thermistor (PTC) or thermal contact
(NC contact)

c2

~

Brake rectifier supply voltage

The brake rectifier is installed in the motor
terminal box

c3

~

c4

S1

Switch for disconnection on the DC side

c5

S2

c6

−PTC

Motor temperature monitoring

PTC thermistor (PTC) or thermal contact
(NC contact)

+

PE

PE conductor

X20 − Connection of an external brake resistor

Pin

Connection

Description

Data

Connector: female, Harting HAN−Modular

1

BR1

Brake resistor

2

n. c.

Not assigned

3

T1

Thermal contact

4

BR2

Brake resistor

5

n. c.

Not assigned

6

T2

Thermal contact