background image

Electrical installation

Safety engineering

4

l

71

EDKLCFH3024−EER DE/EN 2.0

}

Danger!

Danger to life through improper installation
Improper installation of the safety engineering systems can cause an
uncontrolled restart of the drives.
Possible consequences:

ƒ

Death or severe injuries

Protective measures:
Total cable length between X60 and the connected components (e.g. sensors,
devices, etc.) > 3 m:

ƒ

It is essential to shield the cable installed between X60 and the connected
components:
– Connect the shield at least to X60 in the connector shell.
– If possible, connect the shield to the connected component as well.

Total cable length between X60 and the connected components (e.g. sensors,
devices, etc.) < 3 m:

ƒ

Unshielded wiring is permitted.

)

Note!

Please observe during transport, storage and operation:

ƒ

Cover unused connectors for control connections and interfaces with the
plastic covers provided to preserve the certified safety technology features.

Advertising