PULS PISA10.401 Benutzerhandbuch
Seite 2

Instruction Manual: PISA10 - 24V Protection Module
Bedienungsanleitung: PISA10 - 24V Sicherungsmodul
Technical Data
1)
Technische
Daten
1)
PISA10.401
PISA10.402
PISA10.403
PISA10.404
Rated Voltage
Nennspannung
nom.
DC 24V
DC 24V
DC 24V
DC 24V
Input Voltage Range
Eingangsspannungsbereich
18-30Vdc
18-30Vdc 18-30Vdc
18-30Vdc
Maximum Input Voltage
2)
Maximale
Eingangsspannung
2)
max.
35Vdc
35Vdc 35Vdc
35Vdc
Required Input Voltage for Turning-on of
Outputs
Erforderliche Eingangsspannung zum
Einschalten der Ausgänge
typ.
21.4Vdc
21.4Vdc 21.4Vdc
21.4Vdc
Turn-on Delay of Outputs
14)
Einschaltverzögerung
der
Ausgänge
14)
typ.
270ms
270ms 270ms
270ms
Input Voltage Protection Level
3)
Aktivierung der Eingangsschutzschaltung
3)
min. / max.
20.7Vdc / 22.1Vdc
20.7Vdc / 22.1Vdc
20.7Vdc / 22.1Vdc
20.7Vdc / 22.1Vdc
Output Current
Channel 1
Channel
2
Channel
3
Channel
4
Ausgangsstrom
Kanal 1
Kanal
2
Kanal
3
Kanal
4
nom.
nom.
nom.
nom.
1A
1A
1A
1A
2A
2A
2A
2A
3A
3A
3A
3A
4A
4A
4A
4A
Total Output Current (all 4 channels) Gesamter
Ausgangsstrom
(alle 4 Kanäle)
nom.
4A
8A 12A
16A
Output Current Limitation
12)
Ausgangsstrombegrenzung
12)
min. / max.
13A / 18A
13A / 18A
21A / 30A
21A / 30A
Tripping Behavior
13)
per Channel
Abschaltverhalten
13)
pro Kanal
typ. 0.1s, 1.5A / 0.05s, 2A
0.4s, 2.5A/ 0.1s, 4A 0.17s, 4A / 0.06s, 6A
0.3s, 5A/ 0.07s, 8A
max.
18A for typ. 3ms
18A for typ. 12ms
30A for typ. 8ms
30A for typ. 10ms
Voltage Drop between Input and Output
4)
Spannungsabfall zwischen Ein- und Ausgang
4)
typ.
80mV
110mV 100mV
110mV
Stand-by Current
Ruhestrom
typ.
46mA
46mA 46mA
46mA
Power Losses in Stand-by Mode
Verlustleistung im Leerlauf
typ.
1.1W
1.1W 1.1W
1.1W
Power Losses at typical Output Loads
4)
Verlustleistung bei typ. Ausgangsströmen
4)
typ.
1.2W
1.6W 1.9W
2.4W
Load Capacitors
four outputs total
5)
Lastkapazität
alle 4 Ausgänge zusammen
5)
typ. / min.
16mF / 12mF
56mF / 20mF
48mF / 30mF
76mF / 20mF
Load Capacitors
per channel
6)
Lastkapazität
pro Kanal
6)
typ. / min.
4mF / 3mF
14mF / 10mF
12mF / 8mF
19mF / 13mF
Internal Output Fuse
7)
per channel
Integrierte Ausgangssicherung
7)
pro Kanal
nom.
2A
3A 4A
5A
Minimum Wire Gauge
8)
Kleinster Kabelquerschnitt
8)
min.
0.14mm
2
0.25mm
2
0.34mm
2
0.5mm
2
Degree of Pollution (non-conductive) Verschmutzungsgrad
(nicht leitend)
EN 50178 / 62103
2
2
2
2
Degree of Protection
Schutzart
EN 60529
IP20
IP20
IP20
IP20
Class of Protection
Schutzklasse
IEC 61140
III
III
III
III
Reverse Polarity Protection (Input)
Verpolschutz am Eingang
No / Nein
No / Nein
No / Nein
No / Nein
Return Voltage Resistance
9)
Rückspeisefestigkeit
9)
max.
35Vdc
35Vdc 35Vdc
35Vdc
Parallel Use of Outputs
Parallelschaltung von Ausgängen
No / Nein
No / Nein
No / Nein
No / Nein
Operational Temperature Range Betriebstemperaturbereich
nom.
-25°C - +60°C
-25°C - +60°C
-25°C - +60°C
-25°C - +60°C
Storage Temperature Range
Lagertemperaturbereich
nom.
-40°C - +85°C
-40°C - +85°C
-40°C - +85°C
-40°C - +85°C
Humidity
10)
Feuchte
10)
IEC 60068-2-30
5 - 95% r.H.
5 - 95% r.H.
5 - 95% r.H.
5 - 95% r.H.
Vibration Schwingen
IEC 60068-2-6
2g
2g
2g
2g
Shock Schocken
IEC 60068-2-27 30g 6ms, 20g 11ms 30g 6ms, 20g 11ms 30g 6ms, 20g 11ms 30g 6ms, 20g 11ms
Dimensions
11)
(WxHxD) Abmessungen
11)
(BxHxT)
nom.
45 x 75 x 91mm
45 x 75 x 91mm
45 x 75 x 91mm
45 x 75 x 91mm
Weight Gewicht
max.
140g, 0.31lb
140g, 0.31lb
140g, 0.31lb
140g, 0.31lb
Limited Warranty
Gewährleistung
Years / Jahre
3
3
3
3
1) All parameters are specified at 24Vdc, 25°C ambient temperature and after a 5 minutes run-in
time unless otherwise noted.
2) Absolute maximum continuous input voltage with no damage to the protection module.
3) Once the voltage tries to fall below this value, a protection circuit limits or shuts-off the outputs in
order to maintain sufficient input voltage. Voltage dips below this value can occur up to 200µs.
4) Typical value when all output channels are loaded with 50% of its nominal current.
5) Permissible capacitor, which can be switched-on on the outputs without switching-off of the
protection module. The listed values are valid for the entire temperature range.
Parameters for typical values
Parameters for minimum values
PISA10.401
0.5A resistive load per output
1A constant current load per output
PISA10.402
1A resistive load per output
2A constant current load per output
PISA10.403
1.5A resistive load per output
3A constant current load per output
PISA10.404
2A resistive load per output
4A constant current load per output
6) Permissible capacitor, which can be switched-on for one particular output when only this output is
loaded and all others are not. The listed values are valid for the entire temperature range.
Parameters for typical values
Parameters for minimum values
PISA10.401
with additional 0.5A resistive load
with additional 1A constant current load
PISA10.402
with additional 1A resistive load
with additional 2A constant current load
PISA10.403
with additional 1.5A resistive load
with additional 3A constant current load
PISA10.404
with additional 2A resistive load
with additional 4A constant current load
7) These lead fuses are approved according to UL248 and will only open in case of an internal
failure of the module.
8) For a typical installation in accordance with VDE 0891 and VDE 0100-523 for 30°C ambient
temperature.
9) Loads such as decelerating motors and inductors can feed voltage back to the output of the PISA
module. The figure represents the maximum allowed feed-back voltage.
10) Do not energize while condensation is present.
11) Depth without DIN-rail and signal connector. Add 13mm in depth for plug connector.
12) Provided that the supplying power source can deliver enough current. This current can be drawn
from each individual output regardless whether it is a 1A, 2A, 3A or 4A output. According to the
specified ampacity of the outputs, the current can flow for a shorter or longer period of time
before the protection module switches off all four outputs at the same time.
13) The “timer” for the tripping time starts immediately once the nominal current levels are exceeded.
All output channels will switch-off, if one channel is overloaded. See figure 5 for more values.
14) All outputs turn on at the same time
1) Alle Werte gelten bei 24Vdc, 25°C Umgebungstemperatur und nach einer Aufwärmzeit von 5
Minuten, wenn nichts anderes angegeben ist.
2) Absolute Obergrenze, bei der das Sicherungsmodul noch nicht zerstört wird.
3) Unterhalb dieser Eingangsspannung wird die Schutzschaltung aktiviert, um einen Einbruch
der Versorgungsspannung unterhalb typisch 21V zu vermeiden. Die Ausgangsströme
werden begrenzt nach einer bestimmten Zeit abgeschaltet. Spannungseinbrüche unter
diesen Wert sind auf max. 200µs begrenzt.
4) Typischer Wert, wenn alle Ausgänge mit 50% des Nennstroms belastet werden.
5) Zulässige Gesamtkapazität, die an den vier Ausgängen zugeschaltet werden kann, ohne
Abschaltung des Moduls. Die Werte gelten für den gesamten Temperaturbereich.
Parameter für typische Werte
Parameters für Minimumwerte
PISA10.401
0,5A Widerstandslast pro Ausgang
1A Konstantstromlast pro Ausgang
PISA10.402
1A Widerstandslast pro Ausgang
2A Konstantstromlast pro Ausgang
PISA10.403
1,5A Widerstandslast pro Ausgang
3A Konstantstromlast pro Ausgang
PISA10.404
2A Widerstandslast pro Ausgang
4A Konstantstromlast pro Ausgang
6) Zulässige Kapazität, die an einem Ausgang zugeschaltet werden kann, wenn alle anderen
Ausgänge unbelastet sind. Die Werte gelten für den gesamten Temperaturbereich.
Parameter für typische Werte
Parameters für Minimumwerte
PISA10.401
mit zusätzlich 0,5A Widerstandslast
mit zusätzlich 1A Konstantstromlast
PISA10.402
mit zusätzlich 1A Widerstandslast
mit zusätzlich 2A Konstantstromlast
PISA10.403
mit zusätzlich 1,5A Widerstandslast
mit zusätzlich 3A Konstantstromlast
PISA10.404
mit zusätzlich 2A Widerstandslast
mit zusätzlich 4A Konstantstromlast
7) Nach UL 248 zugelassen und öffnen nur im Falle eines Gerätedefektes.
8) Für eine typische Installation nach VDE 0891 und VDE 0100-523 bei 30°C Umgebung.
9) Bremsende Motoren oder Induktivitäten können Spannung zum Ausgang des PISA Moduls
rückspeisen. Der Wert gibt die maximal zulässige Rückspeisespannung an.
10) Nicht betreiben, solange das Gerät Kondensation aufweist.
11) Tiefe ohne DIN-Schiene und Signalstecker. Zusätzlich 13mm in der Tiefe für Steckverbinder.
12) Vorausgesetzt, die speisende Stromversorgung kann genügend Strom liefern. Dieser Strom
kann auch aus jedem einzelnen Ausgangskanal entnommen werden, unabhängig, ob es ein
1A-, 2A-, 3A- oder 4A-Ausgang ist. Je nach Nennstrom des Ausgangskanals kann dieser
Strom kürzer oder länger fließen bis eine Abschaltung aller vier Ausgänge erfolgt.
13) Der „Timer“ zur Abschaltung startet bei Überschreitung des Nennstroms. Bei Überlast an
einem Kanal werden alle Kanäle abgeschaltet. Siehe auch Bild 5 für weitere Werte.
14) Alle Ausgänge schalten gleichzeitig ein.