PULS PISA11.406 Benutzerhandbuch
Seite 2

PISA11 Instruction Manual
PISA11 Bedienungsanleitung
Technical Data
1)
Technische
Daten
1)
PISA11.401
PISA11.402
PISA11.403
PISA11.404
Rated Voltage
Nennspannung
nom.
DC 24V
DC 24V
DC 24V
DC 24V
Input Voltage Range
Eingangsspannungsbereich
18-30Vdc
18-30Vdc 18-30Vdc
18-30Vdc
Maximum Input Voltage
2)
Maximale
Eingangsspannung
2)
max.
30Vdc
30Vdc 30Vdc
30Vdc
Input current
Eingangsstrom
nom.
4A
8A 12A
16A
Required Input Voltage for Turning-on of
Outputs
Erforderliche Eingangsspannung zum
Einschalten der Ausgänge
typ.
21.4Vdc
21.4Vdc 21.4Vdc
21.4Vdc
Turn-on Delay of Outputs
14)
Einschaltverzögerung
der
Ausgänge
14)
typ.
270ms
270ms 270ms
270ms
Outputs meets NEC-CLASS-2
Ausgänge erfüllen NEC-CLASS-2
Yes / Ja
Yes / Ja
No / Nein
No / Nein
Input Voltage Protection Level
3)
Aktivierung der Eingangsschutzschaltung
3)
min. / max.
21.0Vdc / 21.8Vdc
21.0Vdc / 21.8Vdc
21.0Vdc / 21.8Vdc
21.0Vdc / 21.8Vdc
Output Current
Channel 1
Channel
2
Channel
3
Channel
4
Ausgangsstrom
Kanal 1
Kanal
2
Kanal
3
Kanal
4
nom.
nom.
nom.
nom.
1A
1A
1A
1A
2A
2A
2A
2A
3A
3A
3A
3A
4A
4A
4A
4A
Total Output Current (all 4 channels) Gesamter
Ausgangsstrom
(alle 4 Kanäle)
nom.
4A
8A 12A
16A
Output Current Limitation
12)
Ausgangsstrombegrenzung
12)
min. / max.
9A / 12.7A
9A / 12.7A
16.6A / 23.6A
16.6A / 23.6A
Shutdown Times
13)
at 2x rated current Abschaltzeiten
13)
bei 2x Nennstrom
typ.
1s at 2A
1s at 4A
1s at 6A
1s at 8A
at short circuit
bei Kurzschluss
typ.
110ms
110ms
10ms
10ms
Voltage Drop between Input and Output
4)
Spannungsabfall zwischen Ein- und Ausgang
4)
typ.
41mV
83mV 75mV
101mV
Stand-by Current
Ruhestrom
typ.
43mA
43mA 43mA
43mA
Power Losses in Stand-by Mode
Verlustleistung im Leerlauf
typ.
1.0W
1.0W 1.0W
1.0W
Power Losses at typical Output Loads
4)
Verlustleistung bei typ. Ausgangsströmen
4)
typ.
1.0W
1.3W 1.4W
1.8W
Max. Load Capacitors
5)
per channel Max.
Lastkapazität
5)
pro Kanal
48mF / 41mF
94mF / 43mF
69mF / 22mF
57mF / 11mF
four outputs total
alle 4 Ausgänge zusammen
typ. / min.
135mF / 94mF
124mF / 43mF
69mF / 22mF
57mF / 11mF
Max. Load Capacitors
6)
per channel
Max. Lastkapazität
6)
pro Kanal
typ. / min.
49mF / 41mF
92mF / 73mF
80mF / 49mF
71mF / 45mF
Minimum Wire Gauge
8)
Kleinster Kabelquerschnitt
8)
min.
0.14mm
2
0.25mm
2
0.34mm
2
0.5mm
2
Degree of Pollution (non-conductive) Verschmutzungsgrad
(nicht leitend)
EN 50178 / 62103
2
2
2
2
Degree of Protection
Schutzart
EN 60529
IP20
IP20
IP20
IP20
Class of Protection Schutzklasse
IEC 61140
III
III
III
III
Reverse Polarity Protection (Input)
Verpolschutz am Eingang
No / Nein
No / Nein
No / Nein
No / Nein
Return Voltage Resistance
9)
Rückspeisefestigkeit
9)
max.
30Vdc
30Vdc 30Vdc
30Vdc
Parallel Use of Outputs
Parallelschaltung von Ausgängen
No / Nein
No / Nein
No / Nein
No / Nein
Operational Temperature Range Betriebstemperaturbereich
nom.
-25°C - +70°C
-25°C - +70°C
-25°C - +70°C
-25°C - +70°C
7)
Storage Temperature Range
Lagertemperaturbereich
nom.
-40°C - +85°C
-40°C - +85°C
-40°C - +85°C
-40°C - +85°C
Humidity
10)
Feuchte
10)
IEC 60068-2-30
5 - 95% r.H.
5 - 95% r.H.
5 - 95% r.H.
5 - 95% r.H.
Vibration Schwingen
IEC 60068-2-6
2g
2g
2g
2g
Shock Schocken
IEC 60068-2-27 30g 6ms, 20g 11ms 30g 6ms, 20g 11ms 30g 6ms, 20g 11ms 30g 6ms, 20g 11ms
Dimensions
11)
(WxHxD) Abmessungen
11)
(BxHxT)
nom.
45 x 75 x 91mm
45 x 75 x 91mm
45 x 75 x 91mm
45 x 75 x 91mm
Weight Gewicht
max.
120g, 0.26lb
120g, 0.26lb
120g, 0.26lb
120g, 0.26lb
Limited Warranty
Gewährleistung
Years / Jahre
3
3
3
3
1) All parameters are specified at 24Vdc, 25°C ambient temperature and after a 5 minutes run-in
time unless otherwise noted.
2) Absolute maximum continuous input voltage with no damage to the protection module.
3) Once the voltage tries to fall below this value, a protection circuit limits or shutdown the outputs in
order to maintain sufficient supply voltage. Voltage dips below this value can occur up to 200µs.
4) Typical value when all output channels are loaded with 50% of its nominal current.
5) Permissible capacitor, which can be connected to the outputs without shutdown of the protection
module. The listed values are valid for the entire temperature range.
Parameters for typical values
Parameters for minimum values
PISA11.401
0.5A resistive load per output
1A constant current load per output
PISA11.402
1A resistive load per output
2A constant current load per output
PISA11.403
1.5A resistive load per output
3A constant current load per output
PISA11.404
2A resistive load per output
4A constant current load per output
6) Permissible capacitor, which can be connected to one particular output when only this output is
loaded and all others are not. The listed values are valid for the entire temperature range.
Parameters for typical values
Parameters for minimum values
PISA11.401
with additional 0.5A resistive load
with additional 1A constant current load
PISA11.402
with additional 1A resistive load
with additional 2A constant current load
PISA11.403
with additional 1.5A resistive load
with additional 3A constant current load
PISA11.404
with additional 2A resistive load
with additional 4A constant current load
7) De-rate output current linearly from 20A to 15A (sum of all output currents) between 60°C and
70°C. De-rate the output current equally between the individual outputs.
8) For a typical installation in accordance with VDE 0891 and VDE 0100-523 for 30°C ambient
temperature.
9) Loads such as decelerating motors and inductors can feed voltage back to the output of the PISA
module. The figure represents the maximum allowed feed-back voltage.
10) Do not energize while condensation is present.
11) Depth without DIN-rail and signal connector. Add 13mm in depth for the signal connector if
needed.
12) Provided that the supplying power source can deliver enough current. This current can be drawn
from each individual output for a short period of time regardless whether it is a 1A, 2A, 3A or 4A
output. According to the specified ampacity of the outputs, the current can flow for a shorter or
longer period of time before the protection module shutdown all four outputs at the same time.
13) The “timer” for the shutdown starts immediately once the nominal current levels are exceeded. All
output channels will shutdown, if one channel is overloaded. See Fig. 5 for more values.
14) All outputs turn on at the same time.
1) Alle Werte gelten bei 24Vdc, 25°C Umgebungstemperatur und nach einer Aufwärmzeit von 5
Minuten, wenn nichts anderes angegeben ist.
2) Absolute Obergrenze, bei der das Sicherungsmodul noch nicht zerstört wird.
3) Unterhalb dieser Eingangsspannung wird die Schutzschaltung aktiviert (verzögert um 200µs),
um einen Einbruch der Versorgungsspannung zu vermeiden. Die Ausgangsströme werden
für eine bestimmte Zeit begrenzt und danach abgeschaltet.
4) Typischer Wert, wenn alle Ausgänge mit 50% des Nennstroms belastet werden.
5) Zulässige Gesamtkapazität, die an den vier Ausgängen zugeschaltet werden kann, ohne
Abschaltung des Moduls. Die Werte gelten für den gesamten Temperaturbereich.
Parameter für typische Werte
Parameter für Minimumwerte
PISA11.401
0,5A Widerstandslast pro Ausgang
1A Konstantstromlast pro Ausgang
PISA11.402
1A Widerstandslast pro Ausgang
2A Konstantstromlast pro Ausgang
PISA11.403
1,5A Widerstandslast pro Ausgang
3A Konstantstromlast pro Ausgang
PISA11.404
2A Widerstandslast pro Ausgang
4A Konstantstromlast pro Ausgang
6) Zulässige Kapazität, die an einem Ausgang zugeschaltet werden kann, wenn alle anderen
Ausgänge unbelastet sind. Die Werte gelten für den gesamten Temperaturbereich.
Parameter für typische Werte
Parameter für Minimumwerte
PISA11.401
mit zusätzlich 0,5A Widerstandslast
mit zusätzlich 1A Konstantstromlast
PISA11.402
mit zusätzlich 1A Widerstandslast
mit zusätzlich 2A Konstantstromlast
PISA11.403
mit zusätzlich 1,5A Widerstandslast
mit zusätzlich 3A Konstantstromlast
PISA11.404
mit zusätzlich 2A Widerstandslast
mit zusätzlich 4A Konstantstromlast
7) Zwischen +60°C und +70°C ist eine lineare Stromrücknahme von 20A nach 15A erforderlich.
Gleichmäßige Stromrücknahme zwischen allen Ausgängen erforderlich.
8) Für eine typische Installation nach VDE 0891 und VDE 0100-523 bei 30°C Umgebung.
9) Bremsende Motoren oder Induktivitäten können Spannung zum Ausgang des PISA Moduls
rückspeisen. Der Wert gibt die maximal zulässige Rückspeisespannung an.
10) Nicht betreiben, solange das Gerät Kondensation aufweist.
11) Tiefe ohne DIN-Schiene und Signalstecker. Zusätzlich 13mm in der Tiefe für Signalstecker,
wenn benötigt.
12) Vorausgesetzt, die speisende Stromversorgung kann genügend Strom liefern. Dieser Strom
kann kurzzeitig aus jedem einzelnen Ausgangskanal entnommen werden, unabhängig, ob es
ein 1A-, 2A-, 3A- oder 4A-Ausgang ist. Je nach Nennstrom des Ausgangskanals kann dieser
Strom kürzer oder länger fließen bis eine Abschaltung aller vier Ausgänge erfolgt.
13) Der „Timer“ zur Abschaltung startet bei Überschreitung des Nennstroms. Bei Überlast an
einem Kanal werden alle Kanäle abgeschaltet. Siehe auch Bild 5 für weitere Werte.
14) Alle Ausgänge schalten gleichzeitig ein.