3 technical data, 1 general data and operating conditions, Technical data – Lenze M300 Benutzerhandbuch
Seite 30: General data and operating conditions, En 30

Technical data
General data and operating conditions
3
EN
30
Lenze ¯ MDKSEMA ¯ 3.0
3
Technical data
3.1
General data and operating conditions
Conformity and approval
Conformity
CE
2006/95/EC
Low−Voltage Directive
2004/108/EC
EMC Directive
EAC
TP TC 004/2011
(TR CU 004/2011)
Relating to the safety of low
voltage equipment
Eurasian conformity
TR CU: Technical regulation of Custom Union
TP TC 020/2011
(TR CU 020/2011)
Electromagnetic
compatibility of technical
products
Approval
UL/CSA
UL 61800−5−1
Industrial Control Equipment, File No. E132659
CSA 22.2 No. 274
CCC
GB Standard
12350−2009
Chinese Compulsory Certificate
"Safety requirements of small−power motors"
Protection of persons and device protection
Enclosure
EN 60529
IP55
IP54 with brake
When ready for operation:
¯
Seal unused bore holes for cable glands by
means of blanking plugs!
¯
Seal unused connectors by means of protection
covers or blanking plugs!
¯
Close and bolt cover!
(Earth) leakage current
EN 61800−5−1
> 3.5 mA AC, > 10 mA DC
Observe regulations and safety instructions!
Total fault current
In TN systems, the following earth−leakage circuit breakers may be used: 30 mA,
type B
Additional equipotential
bonding
M5 thread with terminal at the terminal box for the connection of a 6 mm
2
PE
cable
Insulation of control circuits
EN 61800−5−1
Safe mains isolation: Double/reinforced insulation for digital inputs and outputs
Insulation resistance
EN 61800−5−1
Site altitude
0 ... 2000 m Overvoltage category III
2000 ... 4000 m Overvoltage category II
Short−circuit strength
EN 61800−5−1
Motor
To a limited extent, error acknowledgement
required
Motor holding brake
No
Brake resistor
No
Control terminals
Yes
Earth fault resistance
EN 61800−5−1
Connection:
Motor
To a limited extent, error acknowledgement
required
Brake resistor
No
Protective measures against
¯
Short circuit on the motor side during switch−on and during operation
¯
Motor stalling
¯
Motor overtemperature (I
2
xt monitoring)
Cyclic mains switching
¯
Switching
processes/minute
3
¯
Switching
processes/hour
Max. 20
¯
Pause
Mains switching of three times per minute must be
followed by a pause of 9 min.
Supply conditions
Mains connection
Power system
TT, TN
(with an earthed neutral)
Operation permitted without restrictions
Delta network
(phase earthed)
Operation not permissible.
IT system
Operation not permissible.
Voltage deviations
Voltage dips
EN 61800−3
Short−time mains voltage dips (cf. IEC 61000−2−1) may cause disconnection.
Control connections
Supply
24 V DC (19.2 ... 28.8 V) by safely separated power supply unit (SELV/PELV)
Digital inputs
IEC 61131−2, type 1
24 V DC, input resistance 5.6 k
W
Digital output
IEC 61131−2, type 1
24 V DC, max. 50 mA