Dfi •operation, Installation – Weidmuller DFI - 2 channel signal isolator / splitter Benutzerhandbuch

Seite 9

Advertising
background image



en

DFI

•Operation

Summary

The DFI is a Dual Channel, DIN rail mount instrument. Each channel

takes an analogue current or voltage input and provides an isolated
voltage or current output.

•Installation

Caution: In order to meet product safety requirements, these units

must only be installed, by qualified staff, in accordance with the
information given in this manual, using the terminal blocks supplied,
and all relevant national electrical wiring and safety rules must be
followed.

location

Locate the instrument in an area that is free from dust, moisture and

corrosive gases.

powerSupplyRequirements

Check the power supply against the model number before applying

power to the instrument. The unit must be used with a suitable mains
power Supply, ratings are as follows:

Voltage Range

Nominal Voltage

Power

Frequency

100-132 V AC

110 V AC

5 VA

47-63 Hz

200-264 V AC

240 V AC

5 VA

47-63 Hz

12-50 V DC*

24 V DC

5 W (at 24 V DC)

-

*Using a DC power supply that provides this voltage will comply with
the instrument’s UL/CSA listing.

Earth connections attach to a stud on the underside of the case. You

must attach this connection before applying power to the unit.