1

Connections
Strip wires to 7 mm from the ends. Use a suitable ferrule for
multistranded wires (do not solder).
Use 1-8 AWG Cu Wire rated for temperatures above 70 °C Only,
tighten to 4.5 lb-In.
For effective protection from electromagnetic noise, all signal cables
must be shielded, or located on conductive trays or in conduits.
The gland supplied suits a single sheath cable with diameter in the
range 8 to 10 mm. Other cable sizes will require a different gland.

Pipe mount bracket assembly