Setup – Weidmuller LPD450F - Display instrument for outdoor use Benutzerhandbuch
Seite 14

14
• Setup
Changing the set-up
1. Move run mode switch to the upper ‘calibrate/set-up’ position.
. Press the P key.
See table below for details.
Setup Sequence
Setting
Display
Description
Е м
P
S/W Version
v1.01
S/W Version (Note: this table applies to versions 1.00 to 1.09 only)
Mode
SetP
CALb
Select for setup mode
Select for calibrate mode
Toggle
Accept
Damping factor
dF=
2
Introduces the damping factor
Value, e.g., 2
-
Dec
-
Inc
Next
Accept
Transfer
function
FnC=
LInr
Srt
1oo1.5
1oo2.5
CurU
Introduces the transfer function
Linear
Square root
x
1 5
x
2 5
Breakpoint linearisation
-
Next
Next
Next
Next
Next
-
Accept
Accept
Breakpoint
linearistion
display
setup
nP=
5
Introduces the number of breakpoints
e.g., 5 (breakpoints at 4, 8, 12, 16 and 20 mA)
-
Dec
-
Inc
Next
Accept
dp=
.
Introduces the display decimal point position
(max 3 places or
nOdp for none)
-
Shift
Next
Accept
y1=
10.000
Introduces the first breakpoint’s display value
e.g., 10.000
-
Dec
-
Inc
Next
Accept
-
Set display values for each breakpoint
Normal display
setup
dP=
.
Introduces the display decimal point position
(max 3 places or
nOdp for none)
-
Shift
Next
Accept
dLO=
0.0
Display range lower limit
e.g., 0.0
-
Dec
-
Inc
Next
Accept
dHI=
100.0
Display range Upper limit
e.g., 100.0
-
Dec
-
Inc
Next
Accept
Save values
SAVE
Instrument is saving the changes to the setup and returning to normal
operation