Calibration – Weidmuller LPD450F - Display instrument for outdoor use Benutzerhandbuch

Seite 16

Advertising
background image

16

• Calibration

General
The LPD450F is factory calibrated. You should not have to recalibrate the
unit before installation.
Allow the instrument 15 minutes of powered operation (to reach a
stable temperature) before calibration. During calibration allow a few
seconds for signals to stabilise before accepting the value.

Equipment requirements
• A suitable 4-0 mA current source

Input calibration procedure

When the display shows Action/Description

Connect the current source to the inputs and set to 4.00 mA.
Put the run/calibrate switch in calibrate position, select setup mode.

CALb

Press

P

CALn

Press

Å

CALy

Press

P three times

InH=

Set the current source to 20.00 mA
Press

P three times

UPCn

Press

Å

UPCy

Press

P