PowerSupplyRequirements
Check the power supply against the model number before applying
power to the instrument. Micromann modules must be used with a
suitable mains Power Supply, ratings are as follows:

Voltage Range

Nominal Voltage

Power

Frequency

100–132 V AC

110 V AC

6 VA

47-63 Hz

200–264 V AC

240 V AC

6 VA

47-63 Hz

12–50 V DC*

24 V DC

6 W (at 24 V DC)

-

*Using a DC power supply that provides this voltage will comply with
the instrument’s UL/CSA listing.

Connections

Terminal

Signal

1

Not used

Input signals

2

A

3

B

4

B

sense

5

Not used

6

Not used

7

Link to change the set-up

Security Link

8

9

Neutral (−)

Power supply

10

Live (+)

11

Normally Closed

Alarm Channel One

12

Common

13

Normally Open

14

Normally Closed

Alarm Channel Two

15

Common

16

Normally Open

Case

Earthing is via a stud on lower side of case