•Calibration
General
The URT/R is factory calibrated and you can select any input range
without recalibrating the unit. However, if you change the RTD type,
you must calibrate the inputs.
Allow the instrument 1 minutes of powered operation (to reach a
stable temperature) before calibration and, during calibration, allow a
few seconds for signals to stabilise before accepting the value.
Equipment requirements
• A suitable RTD simulator (accurate to 0.0 °C)
Inputcalibrationpoints
Calibrationpoint
Pt100
Ni120
Display
Temperature(°C)
Display
Temperature(°C)
1
-200
-200.0 °C
-80n
-80.0 °C
2
700P
700.0 °C
320n
320.0 °C
3
-100
-100 °C
-80n
-80.0 °C
4
200P
200.0 °C
200n
200.0 °C
Terminalconnectionsforinputcalibration
CalibrationStage
Signaltype
Terminal
RTD Inputs
RTD Simulator A
2
RTD Simulator B
3
RTD Simulator Bsense
4