Setup – Weidmuller URTR - Universal glavanically isolated signal converter Benutzerhandbuch
Seite 18

18
•Setup
Changingthesetup
For setup mode, connect the security link and press the
Å
and
ì
keys simultaneously. The software version will be displayed (flashing). If
you wish to continue, press within 10s.
During setup the
Å
and
ì
keys change values and toggle options.
The key accepts changes and moves to the next item in the setup
sequence (see table).
Note: If you remove the security link during the setup sequence, any
changes you have made will be discarded.
Clearingtrippedalarms
You can acknowledge a tripped alarm by simply pressing the ï key.
SetupSequence
Setting
Display
Description
Е м
ENT
S/W Version
v4.01
S/W Version 4.01 (Note: this information only applies to versions
4.00 to 4.09)
DisplayandInputs
Input type
IP=
P100
n120
Introduces the input type
Pt100 RTD sensor
Ni120 RTD sensor
Toggle
Accept
Display units
dEgC
dEgF
Degrees Celsius
Degrees Fahrenheit
Toggle
Accept
Maximum
input range
rng=
Introduces the display range:
-
Next
°C
°F
Range
Sensor
200C
392F
-99.9 to 200.0 °C or
-99.9 to 392.0 °F
Pt100
700C
1292
-200 to 700 °C or
-328 to 1292 °F
320C
608F
-80 to 320 °C or
-112 to 608 °F
Ni120
210C
410F
-80.0 to 210.0 °C or
-99.9 to 410.0 °F
Toggle
Accept