Alternate Floor Protection

All floor protection materials must be non-combustible ie.
metal, brick, stone, mineral fiber boards). Any combustible
material may not be used.

The easiest means of determining if a proposed alternate floor
material meets requirements listed in this manual is to follow
this procedure.

R-value = thermal resistance
k-value = thermal conductivity
C-value = thermal conductance

1. Convert the specification to R-value;

a. If R-value is given, no conversion is needed.
b. If k-value is given with a required thickness (T) in inches:

R=1/k X T.

c. If C-value is given: R=1/C.

2. Determine the R-value of the proposed alternate floor

protector.

a. Use the formula in Step 1 to convert values not

expressed as “R”.

b. For multiple layers, add R-values of each layer to

determine overall R-value.

3. If the overall R-value of the system is greater than the R-

value of the specified floor protector, the alternate is
acceptable.

Example:
The specified floor protector should be 3/4” thick material with
a k-factor of 0.84. The proposed alternate is 4” brick with a C-
factor of 1.25 over 1/8” mineral board with a k-factor of 0.29.

Step A. Use formula above to convert specifications
to R-value. R=1/k X T= 1/.84 X .75 = .893

Step B. Calculate R of proposed system.

4” brick of C-1.25, therefore
R brick = 1/C = 1/1.25 = 0.80.
1/8” mineral board of k = 0.29 therefore
R mineral board = 1/.29 X 0.125 = 0.431

Total R = R brick + R mineral board=
0.8 + 0.431=1.231

Step C. Compare proposed system R = 1.231 to specified R of
0.893. Since R is greater than required, the system is acceptable.

Definitions:
Thermal conductance =

C = Btu = W

(hr)(ft

2

)(F) (m

2

)(K)

Thermal conductivity =
k = Btu = W = (Btu)
(hr)(ft

2

)(F) (m

2

)(K) (hr)(ft)(F)

Thermal resistance =

R = Btu = (m

2

)(K) = (Btu)(inch)

(hr)(ft

2

)(F) W (hr)(ft

2

)(F)

For the Jøtul F 600 woodstove requires floor protection with
a minimum insulating r value of 0.5.

Alcoves require an r value of 1.6.

Only use replacements parts provided through your Authorized Jøtul dealer.

USA/CANADA

Pos. No.

Pos. No.

Pos. No.

Pos. No.

Pos. No. Description

Description

Description

Description

Description

1

Leg

2

Latch (Side Door)

3

Ash House Complete

4

Ash Door

5

Smoke Outlet

6

Fire Grate

7

Air Valve

8

Bottom

9

Inner Bottom

10

Rear Plate

11

Tube Frame Holder

12

Air Manifold

13

Front

14

Inner Front

15

Side Right

16

Side Left

17

Front Door

18

Ash Lip

19

Top

20

Tube Holder Upper Right

21

Tube Holder Upper Left

22

Tube Holder Bottom Right

23

Tube Holder Bottom Left

24

Inspection Cover

25

Side Door

26

Burnplate Side/Door

27

Baffle Plate

2 8

Top Cover

29

Nut

30

Screw Hexagon Stainless

31

Screw Hexagon

32

Screw Collar Hexagon

33

Screw Hexagon

34

Screw Hexagon Stainless

35

Screw Panh.

36

Washer Blackchromating

37

Washer ELZN

3 8

Screw Cylinder Head

39

Screw Cylinder Head

40

Spring Pin

41

Screw Panh.

42

Screw Hexagon Stainless

43

Screw Allen

44

Screw Collar Hexagon

45

Washer

46

Washer Insul.

47

Gasket (Side Door)

48

Latch Ash Door

49

Gasket (Front Door)

50

Spring

51

Latch Bolt Side Door

52

Sleeve

53

Wooden Knob + Small Parts

54

Hinge Pin Front/Side Door

56

Wooden Knob Ash Door

57

Ash Pan

5 8

Handler for Air Vent

59

Nut M10

60

Handle Ash Door Complete

61

Clip

62

Hinge Pin, Ash Door

63

Gasket (Ash Door)

64

Gasket (Ash House)

65

Gasket (Top)

66

Insulation Blanket

67

Gasket (Smoke Outlet)

6 8

Glass

69

Catch

70

Refractory Brick

71

Insulation Blanket Top

72

Tube Rear

73

Tube, Middle and Front

75

Heat Shield Bottom

7 7

Heat Shield Rear + Top Exit

7 8

Latch Bolt Front Door

79

Glass Clip

80

Gasket (Door Glass)

81

Gasket (Top Cover)

8 2

Latch (Front Door)

8 3

Washer

84

Air Chamber Complete

8 5

Adapter Outside Air

Advertising