VEGA VEGASON S 61 Benutzerhandbuch

Seite 31

Advertising
background image

storage detects and marks these false echoes, so

that they are no longer taken into account for the

level measurement. A false echo memory should

be created with empty vessel so that all potential

interfering reflections will be detected.

Gating out of false signals

Change now?

Proceed as follows:
1 Move from the measured value display to the

main menu by pushing [OK].

2 Select the menu item "Service" with [->] and

confirm with [OK]. Now the menu item "False

signal suppression" is displayed.

3 Confirm "False signal suppression - Change

now" with [OK] and select in the below menu

"Create new". Enter the actual distance from

the sensor to the product surface. All false

signals in this area are detected by the sensor

and saved after confirming with [OK].

Note:

Check the distance to the product surface,

because if an incorrect (too large) value is

entered, the existing level will be saved as

false signal. The filling level would then no

longer be detectable in this area.

Copy sensor data

This function enables reading out parameter

adjustment data as well as writing parameter

adjustment data into the sensor via the indicating

and adjustment module. A description of the

function is available in the operating instructions

manual "Indicating and adjustment module".

Copy sensor data

Copy sensor data?

Reset

Basic adjustment

If the "Reset" is carried out, the sensor resets the

values of the following functions to the reset values

(see chart):

1)

Function

Reset value

Max. adjustment

0 m(d)

Min. adjustment

Meas. range end in m(d)

2)

Medium

Liquid

Vessel form

not known

Damping

0 s

Linearization

linear

Sensor-TAG

Sensor

Displayed value

Distance

Current output - characteristics 4 … 20 mA

Current output - max. current

20 mA

Current output - min. current

4 mA

Current output - failure

<3.6 mA

Unit of measurement

m(d)

The values of the following functions are not reset

to the reset values (see chart) with "Reset":

Function

Reset value

Lighting

no reset

Language

no reset

HART mode

no reset

Factory setting

Like basic setting, in addition special parameters

are reset to default values.

3)

Pointer

The min. and max. distance and temperature

values are reset to the actual value.

Optional settings

Additional adjustment and diagnosis options such

as e.g. scaling, simulation or trend curve presen-

tation are shown in the following menu schematic.

1)

Sensor-specific basic adjustment.

2)

Depending on the senso type, see "Technical data".

3)

Special parameters are parameters which are set customer-specifically on the service level with the adjustment

software PACTware™.

VEGASON S 61

31

Set up with the indicating and adjustment module

32944

-02

-070301