Rotary actuator

11

Torque limitation option
The limitation of the torque is separate for both
setting directions via a potentiomenter each which
can be set from 0 to maximum value. On reaching
the torque limit a signal with U=U

rated

is given via

terminal 26. The signal can take a maximum load
of 0,1 A.
After addressing the torque limit - as long as the
control signal lasts - the expected torque is
checked every 8 s. In case of fall off, the preselected
value is readjusted by briefly switching on the
motor.

Reset option in case of power cut
In the case of a power cut, rotary actuators with
integrated emergency power supply automatically
drive the setting element to a defined limit position.
The resetting in the case of a power cut includes
the torque limit.

Setting notes for appliances with torque limit
and resetting in case of power cut
Torque limitation option
(see diagram inside cover)

Potentiometer 1 Setting the max. torque for
setting direction "CLOSED",
infinitely variable from 0 to rated torque
Potentiometer 2 Setting the max. torque for
setting direction "OPEN", infinitely variable
from 0 to rated torque

Reset option in case of power cut

Switch S1
Position 1 Safety position currentless
"CLOSED“;
Position 2 Safety position currentless
"OPEN“;

Significance of potentiometers 1 and 2 as for the
torque limitation.
The limit switch cams are adjusted at the factory
and protected with varnish .
Attention: Readjustment of the cams negates the
warranty!

Notes about NC cells
The NC cells are fully recharged 10 hrs after
connecting the operating voltage (connections1
and 4). It is advisable to replace the NC cells
routinely every two years.

Note for additional limit switches
The microswitches S5 to S8 serve as position
indicators.
! For mechanical reasons, the limit switch is
not just operated by the cam at one point but
across an area. If the response only occurs
at one point, two additional limit switches
are required for the respective overlap.

Example:
Actuator with 180

° rotation angle and two

additional limit switches

zusätzliche Endschalter

Stellbereich

Endlagen-Endschalter

zusätzliche Endschalter

Stellbereich

Endlagen-Endschalter

Überlappung

Further information in manual.
Order No. 1 893 118 Q

• Rotate S3 tripping cam in opposite direction

until S3 switches.
(S3 and S4 are pressed in centre position.)

additional limit switch

position area

limit position - position switch

additional limit switch

overlap

position area

limit position - position switch