14

Fault finding

Problem

Test

Fault

Remedy

Motor does not run

Check connection. Is

– Motor without voltage

– Fix connection

– no humming

voltage applied to

– Power supply not in order

circuit board?

– Thermal circuit

Motor overheated?

breakerhas switched

– Allow motor to cool,

off motor due to

avoid further overloading

overheating.

Are several actuators

– Limit switch welded

– Drive acuators

connected in parallel?

separately or via relay

– Capacitor defective

– Replace capacitor

and limit switch

– Motor humming

Is it possible to turn

– Gear or motor

– Return actuator to

the actuator by

blocked

factory

emergency manualr
operation or only with
great difficulty?

Fuse comes into

Is the drive connected

– Short circuit caused by

– Fix connection

action.

properly? No.

connection fault.

Return actuator to

Resistance of

Winding defective.

factory.

windings outside
tolerance range.

1)

Motor runs on

– Tripping cams do

– Limit switch lug or

– Exchange circuit board

not operate limit switch

block bent

with limit switch block

– Limit switch not

– Limit switch

– Exchange circuit board

working (audibly)

mechanically defective

with limit switch block

– Microswitch operates

– Set tripping cams

too late

according to instructions

Wrong direction of

Compare connections

– Connections

- Connect according to

rotation

with circuit diagram

interchanged

circuit diagram.

(3-position regulator)

Potentiometer

Does the potentiometer

– Defective clutch.

- Replace clutch (if no

doesn't follow

clutch slip? Yes.

success also poten-

the movement

tiometer)

(completely)

Does the potentio-

– Defective potentio-

– Replace potenti-

meteraxis rotate? No.

meter

ometer.

External control

Does the potentio-

– Outer control or

– Fix outer circuit

doesn't work via

meter voltage follow

relay circuit defective

potentiometer

the movement? Yes.
No.

– See "Potentiometer

doesn't follow".

1)

230 V 184–202

Ω 110 V 35,2–38,8 Ω

Resistance measurement on plug 3001-186 from middle contact.