Fine calibration (zero point and full scale), 4 functions and operation – JUMO 707020 dTRANS T02 LCD - Four-Wire Transmitter Operating Manual Benutzerhandbuch

Seite 57

Advertising
background image

19

4 Functions and operation

Fine calibration (zero point and full scale)

Fine calibration can be used to adjust the zero point and the slope
of the output signal. Here, too, the

d and i buttons are available

for altering the appropriate value, and for accepting it by pressing
the

q button.

The actual measured value is produced at the output. At zero point
(OUTL), this should correspond to the output signal 0%, at full scale
(OUTH), to the output signal 100%.

If the zero point OUTL is corrected, the full-scale value OUTH should
also be adjusted, because of the interaction between both parame-
ters.

Resetting the fine calibration

During fine calibration, the zero point OUTL or full scale OUTH can be
reset to their respective default values (basic setting) by using the
button combination

q + i. OUTL and OUTH can only be reset sepa-

rately, not simultaneously.

Fine calibration can also be reset through the PC setup program.

OUTL

OUTH

Input signal

Output signal