Teach-in, 4 functions and operation – JUMO 707020 dTRANS T02 LCD - Four-Wire Transmitter Operating Manual Benutzerhandbuch

Seite 58

Advertising
background image

20

4 Functions and operation

Teach-in

The “Teach-in” parameter serves to define the 0% value. The actual
value that is present at the output will become a 0% value through
“Teach-in” programming.

This value is accepted by pressing the

d or i button and executed

with

q. After a time-out without acceptance, the old value will be

available again.

Example:

The position of a valve is detected by a potentiometer. The potenti-
ometer covers the range 50 to 150

Ω

, with 50

Ω

corresponding to the

valve closed. The range is programmed as follows:

- potentiometer 50 — 150

Ω

- output 0 — 20mA

Assumption:

However, because of mechanical tolerances, the potentiometer po-
sition with the valve closed is 52

Ω

, which results in an output cur-

rent of 0.4mA. Thanks to the “Teach-in” function, this error can be
eliminated as described below:

- close valve

- call the parameter level and select OFFS

(0.4mA should then be present at the output).

- press the

d or i button – the output must now

change to 0mA.

- confirm alteration by pressing

q.

- exit the parameter level (either after a time-out of 20sec or by

simultaneously pressing

q + d.

Advertising