21

5 Configuration and parameter tables

You can record your settings in the configuration and parameter ta-
bles below, in the position (column) marked with

. The factory

settings are shown on a gray background (

).

Parameters at the parameter level

Parameters at the configuration level

Measurement input

Para-

meter

Explanation

Value range factory

setting

X

Al1

Limit value of
limit comparator 1

-1999 to
+9999 digit

0

AL 2 Limit value of

limit comparator 2

-1999 to
+9999 digit

0

OUTL Fine calibration 0%

(zero)

see “Fine calibration (zero point

and full scale)” on page 19

OuTH Fine calibration 100%

(full scale)

see “Fine calibration (zero point

and full scale)” on page 19

OFFS Teach-in

see “Teach-in” on page 20

C111 Transducer

X

0

Resistance thermometer in 3-wire circuit

1

Resistance thermometer in 4-wire circuit

2

Resistance thermometer in 2-wire circuit

3

Thermocouple

4

Voltage up to 1000mV

5

Voltage up to 10V

6

Current

7

Resistance transmitter

8

Potentiometer 3-wire circuit

9

Potentiometer 4-wire circuit

10

Potentiometer 2-wire circuit

Advertising