WTC 600 LP / MP

6

Maintenance and Care

Version 06/05

3.2

During Operation

3.2.1

Control and Corrective Action Intervals

d…daily, w…weekly, m… monthly

3.2.2

Sand and Activated Carbon Filter

During operation, the sand and activated carbon
filter control indicates the actual time. To change
the indication:

• Press button (32) for approx. 5 s; the display

(31) indicates the time of the regeneration.

• Press button (32) briefly; the display indicates

the number of regenerations.

• Press the ADVANCE key button briefly; the

display indicates the number of days and hours
since the last regeneration.

Drinking water quality is ensured only when the following control intervals are met. In case
deviations from the desired condition can not be eliminated through the measures mentioned,
the drinking water production must be stopped and the Kärcher Service must be notified.

Interval Check/Activity

Target/Purpose

In Case of Deviation

d

Level, metering container

Sufficient amount/filling

Fill up; mixing chemi-
cals,
see Section 3.2.6

Air bubbles in metering line

No air bubbles

Bleed metering pump,
see Section 3.2.3

Flow of drinking water

based on the operational start-up value

Reduction of the drinking water
flow up to 10 %

Fine adjustment,
see Section 3.2.5 (1)

Drinking water conductance value

based on the operational start-up value

Increase of the drinking water
conductance value up to 10 %

Fine adjustment,
see Section 3.2.5 (2)

Pressure difference between pump
and concentrate pressure

15 % maximum above start-up
difference

See Section 3.2.5 (3)
Kärcher Service

Hour meter for sand und activated
carbon filter

*

* for switching over the indication, see Section 3.2.2

Backwashing has occurred
within the past 24 h

Kärcher Service

Pressure difference, fine filter

≥ 0,8 bar

Replace fine filter,
see Section 3.2.4

Visual inspection of the equipment

No leakage

Kärcher Service

w

Fill out operating log

m

Clean and flush the metering
container

Visually check the untreated water
pump

No damages/leaks detectable Kärcher Service

Float switch in the drinking water
tank

No operational malfunctions
detectable

Kärcher Service