6technical data – Karcher WATERCLEAN A 2011201 Benutzerhandbuch

Seite 24

Advertising
background image

WTC 600 LP / MP

12

Technical Data

Version 06/05

6

Technical Data

Parameter

WTC 600 LP

WTC 600 MP

Ambient temperature

+1 °C – +50 °C

Storage temperature (upon delivery)

to –10 °C

Humidity

<100 % r.F.

Supply voltage

3*400 V 50 Hz

*

1*230 V 50 Hz

*

* depending on supply by the customer

Pre-filter controls: prim./sec.

230 V/12 V 50 Hz

Metering pumps

220 – 240 V 50 – 60Hz

Electrical protection

16 A

Connected load

2.2kW

2.2 kW

Effective power consumtion

1.5 kW

2.2 kW

Minimum temperature of untreated water

+5 °C

Maximum temperature of untreated water

+35 °C

Reference temperature

+15 °C

pH-value of untreated water

6 – 9.5

pH-value cleaning agent for cleaning the equipment

3 – 11

System intake pressure

2 – 6 bar

Capacity range

15000 l/day (±15 %)

Maximum drinking water supply

650 l/h

Dimensions: H x W x D

WTC 600 LP/MP

1800 x 660 x 720 mm

WTC 600 LP/MP - A

1800 x 1120 x 720 mm

WTC 600 LP/MP - AM

1800 x 1120 x 720 mm

Weight, in delivery condition

WTC 600 LP/MP

135 kg

WTC 600 LP/MP - A

155 kg

WTC 600 LP/MP - AM

175 kg

Designed for untreated water based on a
maximum salt content of

2000 ppm

5000 ppm

Advertising