Control heads with communication
ELECTRICAL CONNECTION
Bus drive via DeviceNet
ELECTRICAL CONNECTION
In brief
(MAC ID = Medium Access Control Identifier)
DIP1 = off = 0 / DIP1 = on = 1
MAC ID = DIP1*2
0
+ DIP2*2
1
+...+ DIP6*2
5
Bus drive via AS interface standard
ELECTRICAL CONNECTION
No. of valves
max. 3 x 1 W
Bus connection
- ASI shaped cable
- 4-pole plug with round cable
- 4-pole plug at control head
I/O-Code
7 hex (4 outputs, 4 inputs)
ID-Code
F hex (for bit configuration see table)
extended ID codes 1 and 2 = F hex
Profile:
7.F
Setting the netw
ork
data rate
d to a
LED
g screws
s) for
y switches
ckwise:
y switch
upwards
iclockwise:
y switch
ownwards
Bit configuration
ASI printed card
Status displa
y
- Loose the 2 screws of connector
- Take off the upper part
- Insert the shaped cable with tight fit
- Put on the upper part again
- Tight the screws - ready!
1 brown, ASI+
2 n.c.
3 blue, ASI-
4 n.c.
Bus line DeviceNet 4-wire cable plus shield which must meet
the DeviceNet specification; with the cable both information
(data) and energy (voltage supply for actuators and sensors) are
transmitted. Before commissioning, read in the EDS file supplied
on diskette or from the Internet.
Pins 2+3: voltage supply 11 to 25 V DC
max. power conumptin 5 W when all valves are actuated
Pins 2+3
Bus drive via DeviceNet
Configuration of the control head with 8 DIP switches
- DIP switches 1 to 6
DeviceNet address
- DIP switches 7and 8
network data rate
DIP 7
DIP 8
Network data rate
Line length
off
off
125 kBaud
max. 500 m
on
off
250 kBaud
max. 250 m
off
on
500 kBaud
max. 100 m
on
on
not allowed
For process data and max. length when using drop
lines, see Instr. type 1066.
De
viceNet
printed car
d
to DeviceNet specification (see Instr. type 1066)
LED Power single-colour (green):
LED on = voltage present
LED MNS
two-colour (red-green): status indication
GB
GB
GB
GB
Data
lines
CAN_H
white
CAN_L
blue
Drain (shield) n.c.
V -
black
V +
red
Data bit
D3
D2
D1
D0
Output
yellow LED
valve 3
valve 2
valve 1
Input
nc
proximity
switch 3
proximity
switch 2
proximity
switch 1
Parameter
bit
P3
P2
P1
P0
not connected
Value 0 = Off; value 1 = On
LED green
LED red Bus status
off
off
POWER OFF
off
on
No data traffic (watchdog expired
with slave address non-zero)
on
off
ok
flashes
flashes
Periphery error (overload in
sensor supply)
flashes
on
Slave address = 0
off
flashes
RESET
LED
green
LED
red
LED
yellow
Settings of the
D
e
viceNet address
Status
indication
DIP 1
[2
0
=1]
DIP 2
[2
1
=2]
DIP 3
[2
2
=4]
DIP 4
[2
3
=8]
DIP 5
[2
4
=16]
DIP 6
[2
5
=32]
MAC
ID
off
off
off
off
off
off
0
on
off
off
off
off
off
1
off
on
off
off
off
off
2
...
...
...
...
...
...
...
off
on
on
on
on
on
62
on
on
on
on
on
on
63
Control heads with communication
➀
Bus connection - Connector for distribution to ASI shaped
cable
Bus drive via DeviceNet
4-pole M12 plug on control head
Bus drive via AS interface standard
Bus line ASI Unshielded two-wire conductor over which both
information (data) and energy (voltage supply for actuators and
sensors) are transmitted.
-
➁
ASI-Version A/B-Slave see Operating Instructions type 1066
Control heads with communication