ARI Armaturen Elektrischer Schubantrieb FR 1.2 DE Benutzerhandbuch

Seite 10

Advertising
background image

P100001973

- 10 -

LED display

Engineering and installation notes

Fitting outdoors.

Auxiliary changeover switch:

Warnings

CE conformity

The display consists of two dual-colour LEDs (red / green).
Both LEDs flashing green: waiting time (45 s) after end of spring return function
Both LEDs flashing red:

initialisation procedure

One LED flashing green:

drive running, moving according to LED

One LED lit green:

drive stationary, last direction according to LED

One LED lit red:

endposition reached; valve position (open or closed) according to LED.

No LED lit:

no voltage supply (terminal 21)

Both LEDs are flashing

red and green: drive is in manual mode

Penetration of condensate or dripping water, etc. along the valve spindle into the drive should be
avoided.
The drive is plugged directly onto the valve and is fixed with screws (no further settings are needed).
The drive is automatically connected to the valve spindle. Depending on the condition of the device
when delivered and its type, the stroke of the drive spindle is 0% or 100%.
The housing contains three breakthrough-type cable leadthroughs which are broken open
automatically when the cable leadthrough is screwed in.
The DC motor/electronics concept guarantees parallel running of several valve drives of the same
type. The cross-section of the connecting cable should be selected according to the line length and
the number of drives. With five drives connected in parallel and a line length of 50 m, we recommend
using a cable cross-section of 1,5 mm2 (power consumption of the drive 5).
The drive can be assembled with a maximum of one 230 V module and an additional double
auxiliary switch.

If the devices are fitted outdoors, we recommend that additional measures be

taken to protect them against the effects of the weather.
Additional technical information
The blue housing, comprising the front section, rear section and connection cover, only serves the
purpose of a cover. The crank for manual adjustment is located on the front. The DC motor, the
control electronics, the supporting components and the maintenance-free gear are accommodated
in the housing.

Switching capacity max. 250 V~, min. current 250 mA at 12 V (or 20 mA at 20 V)
Switching capacity max. 12...30 V=, max. current 100 mA

If the temperature of the medium in the valve is high, the drive columns and the shaft may also

reach high temperatures.

Drives with safety functions must be regularly checked to see that they are in working order (trial

run).

If a failure of the final control element could cause damage, additional protective precautions

must be taken.

It is forbidden to dismantle the springs in the device due to the high risk of injuries.

?

?

?

?

?

?

EMC Directive 2004/108/EC

Machinery Directive 98/37/EEC (II B)

Low Voltage Directive 2006/95/EC

EN 61000-6-1

EN 1050

EN 60730-1

EN 61000-6-2

EN 60730-2-14

EN 61000-6-3

Over-voltage category III

EN 61000-6-4

Degree of pollution II