Technical data, Rated data, Output data – Lenze ELCAFHIxxx4E34NNPM Highline Benutzerhandbuch
Seite 62: Rated values for internal brake chopper

Technical data
Rated data
l
62
EDKLCFH1134−EPM DE/EN 1.0
Output data
Voltage
Frequency
Current (T
a1
)
1)
Current (T
a2
)
2)
Number
of phases
Typ
[V]
[Hz]
[A]
[A]
ELCAFHI5524
0 ... 400/500
0 ... 480
13.0/11.4
8.7/7.1
3
ELCAFHI7524
0 ... 400/500
0 ... 480
16.5/14.5
10.3/9.1
3
ELCAFHI1134
3)
0 ... 400/500
0 ... 480
23.5/20.7
14.7/12.9
3
ELCAFHI1134
4)
0 ... 400/500
0 ... 480
18.8/16.6
11.8/10.3
3
1)
Ta1 = max. 40 °C ambient temperature during operation
2)
Ta2 = max. 55 °C ambient temperature during operation
3)
Operation with mains choke ELN3−0150H024_001
4)
Operation without mains choke
Power loss P
V
[W]
Type
when operating with rated output current I
aN
when controller is inhibited
ELCAFHI5524
349
40
ELCAFHI7524
430
ELCAFHI1134
580
Rated values for internal brake chopper
Switching threshold
(adjustable)
Minimum
brake resistor
Continuous current
Continuous braking
power
Type
U
BRmax
[V]
R
Bmin
[
W]
I
BRd
[A]
P
Bd
[kW]
ELCAFHI5524
790
27
29.3
23.1
ELCAFHI7524
790
27
29.3
23.1
ELCAFHI1134
790
27
29.3
23.1