Electrical installation, Safety engineering – Lenze ELCAMWIxxx4SNNPSNN (LCU 121) Benutzerhandbuch
Seite 62

Electrical installation
Safety engineering
l
62
EDKLCMW3024−SPS DE/EN 7.0
Detail characteristics of the safe inputs and safe outputs
Signal
Specification
Min.
Typ.
Max.
I1A, I1B
I2A, I2B
I3A, I3B
I4A, I4B
PLC input, IEC−61131−2, 24 V, type 1
LOW signal
[V]
−3
0
5
Input current
[mA]
15
HIGH signal
[V]
15
24
30
Input current
[mA]
2
15
Input capacitance
[nF]
3.3
Switch−off time (depending on the standard device)
[ms]
2
4
Switch−on time
[ms]
2
4
Input delay (tolerated test pulse)
[ms]
1
CLA, CLB
PLC output, IEC−61131−2, 24 V DC, 50 mA
Supply voltage of the outputs
[V]
18
24
30
LOW signal
[V]
0
0.8
HGH signal
[V]
17
24
29
Output current
[mA]
50
Width of test pulse
[
ms]
750
Frequency of test pulse
[s]
1
1.8
3
Specific resistance of a passive sensor
[k
W]
2
O1A, O1B
O2A, O2B
PLC output, IEC−61131−2, 24 V DC, short−circuit−proof
Supply voltage of the outputs
[V]
18
24
30
Output voltage for LOW signal
[V]
0
0.8
Output voltage for HIGH signal
[V]
17
24
29
Output current
[mA]
500
Width of test pulse
[
ms]
750
900
Frequency of test pulse
[s]
1
1.8
3