Power Supply Requirements
Check the power supply against the model number before applying
power to the instrument. AI8 modules must be used with a suitable
mains Power Supply, ratings are as follows:

Voltage Range

Nominal Voltage

Maximum Power

Frequency

Fuse value

90-250 V AC

-

14 VA

47-63 Hz

500 mA

90-250 V DC*

-

14 VA

-

20-35 V DC*

24 V DC

14 W (at 24 V DC)

-

1 A

*Using a DC power supply that provides this voltage will comply with
the instrument’s UL/CSA listing.
Since the power supply is permanently connected, the building wiring
must be connected through a suitably marked switch or circuit breaker
in close proximity and within easy reach of an operator.

Symbols
The instrument labels use symbols in accordance with IEC61010-1:

- Consult documentation;

- Direct Current;

- Both direct

and alternating current;

Connections
Strip wires to 7 mm from the ends. Use a suitable ferrule for multi-
stranded wires (do not solder).
Use 1-8 AWG Cu Wire rated for temperatures above 70 °C Only,
tighten to .5 lb-In.
For effective protection from electromagnetic noise, all signal cables
must be shielded, or located on conductive trays or in conduits.