Equipment requirements

• A suitable current/voltage source (must be able to generate

0.00 mA and 10.00 V to ±0.05 % or better accuracy)

• An accurate digital multimeter (accurate to 0.05 mV and ±0.1 μA)

Terminal Connections for Input calibration

Calibration Stage

Signal type

Input Channel

1

2

3

4

5

6

7

8

Inputs

Signal source (+)

1

2

4

5

7

8

10

11

Signal source (−)

3

6

9

12

Input calibration procedure
1. Select the channel you wish to calibrate (see diagram above).
. Press ENT , display will show: Short Input 1
. Short the input terminals for that channel.
. Press ENT, Display will show Processing... message.
5. When the display shows Input1 @ 20.00 mA connect

0.00 mA dc to the input.

6. Press ENT, Display will show Processing... message.
7. When the display shows Input1 @ 10.00 V connect

10.00 V DC to the input.

8. Press ENT, Display will show Processing... message.
. At the ‘Continue?’ prompt, select ‘Yes’ to go the next Input

Channel or ‘No‘ to go back to the calibration menu.

10. At the ‘Save?’ prompt, select ‘Yes’ to permanently save the

values or ‘No‘ to use the new values until next power up.