Calibration mode – Weidmuller AI8 - Multi channel signal transmitter Benutzerhandbuch

Seite 30

Advertising
background image

0

Communications Setup
Allows you to configure the RS/RS85 outputs.

Display Setup
Sets up display scrolling options.

User Definitions
The ‘User’ Definition’ menu allows you to set one ‘User Defined’
linearisation curve for use by any of the inputs. It also allows you to set
up character sequences for four ‘User Defined’ Engineering Units.

• Calibration Mode

General
The AI8 is factory calibrated. Once calibrated it will operate with
any input or output format without calibration. You should not have to
calibrate the unit before installation.
Allow the instrument 15 minutes of powered operation (to reach a
stable temperature) before calibration.
During calibration allow a few seconds for signals to stabilise before
accepting the value.

ENT

EXIT

EXIT

EXIT

ENT

Calibration Mode
Prev Next

To Run
Mode

Calibrate P.I.N
101

Defau t P N = 101

Lower PIN

Calibrate Output
Prev Next

ENT

Calibrate Input
Prev Next

Select which input to calibrate

Previous Output Channel

ENT Calibrate Output

Next Output Channel

EXIT Exit

Calibrate
Output 1

Raise PIN

ENT

Input calibration Procedure (see below)

EXIT

MENU

ENT

Invalid PIN
Menu->Retry