Weidmuller DPADMA - Universal glavanically isolated signal converter Benutzerhandbuch

Seite 16

Advertising
background image

16

Alarm connections
The DPA has a high inbuilt immunity to noise spikes caused by
switching inductive loads like solenoids or relay coils. However, it
is important to use suppression capacitors across inductive loads
to preserve the relay contacts and to reduce the effect of switching
spikes on nearby circuits.
The alarm outputs are dual SPDT relay contacts with built in
suppression capacitors fitted across the normally open and common
contacts.

DPA/DMA

1 2

2-wire

Transmitter

+

Twisted pair cable

Ground cable shield at transmitter end only

DPA/DMA

2

4

DC mA

source

+

Twisted pair cable

Ground cable shield at signal source only

Input connection diagrams for mA current inputs.