Modifications, Eb a c f – Weidmuller DPADMA - Universal glavanically isolated signal converter Benutzerhandbuch

Seite 20

Advertising
background image

0

Modifications

Removing the left hand side plate
1. Remove the six self tapping

screws marked A-F (disconnect
power first).

. Remove the two countersunk

bolts marked G & H.

3. Remove the left hand side plate

and note the position of the
insulator covering the power
supply board.

. You can now ease the power supply board from the housing.
Warning: take great care when operating AC powered instruments
without the housing as there are high voltages present.
Note: bolt the power supply board and insulator to the side plate
before reassembly.

Removing the electronics from the housing
1. Remove the left hand side plate as described above.
. Remove the six self tapping screws from the right hand side plate

(equivalents of A thru F on the left side).

3. Remove the front cover.
. Slide the base extrusion off the terminal board.
5. Remove the two bolts from the right hand side plate
(equivalent of G & H on the left side). Note the position of the insulator.
Assembly is the reverse of the disassembly procedure.
Warning: Correct insulator location is essential to product safety.

LEFT HAND SIDE V EW

E

B

A

C

F