Weidmuller DPADMA - Universal glavanically isolated signal converter Benutzerhandbuch

Seite 17

Advertising
background image

1

Cable preparation and installation
For effective protection from electromagnetic noise, all signal cables
must be shielded, or located on conductive trays or in conduits.
Use 1-8 AWG Cu Wire rated for temperatures above 0 °C Only,
tighten to .5 lb-In. Strip wires to  mm from the ends. Use a suitable
ferrule for multistranded wires (do not solder).

Input Signal Cabling
Use suitable twisted pair cable for the input signal connection.

Connections

Terminal

Signal

1

24 V DC (out)

Input signals

2

Signal +

3

Not Used

4

Signal −

5

Not Used

6

7

8

9

Neutral (−)

Power supply

10

Live (+)

11

Normally Closed

Alarm channel one
(Relay Contacts)

12

Common

13

Normally Open

14

Normally Closed

Alarm channel two
(Relay Contacts)

15

Common

16

Normally Open

Protective Earth

Via stud on the underside of the case

Note 1: Double lines indicate isolation between ports

- Caution risk of electric shock (screw terminals can carry high voltages)