18
Connections
Strip wires to 7 mm from the ends. Use a suitable ferrule for multi-
stranded wires (do not solder).
Use 12-28 AWG Cu Wire rated for temperatures above 70 °C Only,
tighten to . lb-In.
For effective protection from electromagnetic noise, all signal cables
must be shielded, or located on conductive trays or in conduits.
Terminal
Signal
1
24 V DC (out)
Input signals
2
Current +
3
Common −
4
Voltage +
5
Not used
6
7
Link to change the set-up
Security Link
8
9
Neutral (−)
Power supply
10
Live (+)
11
Channel one
Alarm outputs
12
Channel two
13
Common
14
Output +
Analogue outputs
15
Current −
16
Voltage −
Case
Earthing is via a stud on lower side of case