22 outputcalibrationprocedure – Weidmuller UCVAR - Universal glavanically isolated signal converter Benutzerhandbuch
Seite 22
Advertising
22
Outputcalibrationprocedure
Whenthe
displayshows
Action/Description
м
Е
ENT
Put the instrument in setup mode and scroll through the main menu
COPn
Press
Å
or
ì
COPy
Calibrate Outputs?
Toggle
Start
Measure the output current
I=0
The output current should be 0.00 mA
(Use the keypad to adjust the value as required)
Increase Decrease Accept
I=20
The output current should be 20.00 mA
Increase Decrease Accept
Measure the output voltage
E=0
The output voltage should be 0.00 V
Increase Decrease Accept
E=10
The output voltage should be 10.00 V
Increase Decrease Accept
Save
Instrument will save values and return to normal operation (using the new values).
Note: Do not remove the power while the save message is on display.